Fluke 43B

"V/A/Hz Display

True-rms voltage (ac + dc)
Ranges:
5.000 V, 50.00 V, 500.0 V, 1250 V*
Accuracy:
?(1% + 10 counts)

True-rms current (ac + dc)
Ranges: 50.00 A, 500.0 A, 5.000 kA, 50.00 kA, 1250 kA
Accuracy:
?(1% + 10 counts),

Frequency
Ranges:
10.0 to 15.0 kHz
Accuracy:
?(0.5% + 2 counts)

CF Crest factor
Ranges:
1.0 - 10.0
Accuracy:
?(5% + 1 count)

<>Power Display
Watts, VA, VAR
1-phase and 3-phase,3 conductor balanced loads
Ranges:
250 W - 1.56 GW
Accuracy:
?(4% + 4 counts) Fundamental Power
Accuracy:
? (2 % + 6 counts) Total Power

PF Power Factor
Range:
0 - 1.0
Accuracy:
?0.04
DPF Displacement Power Factor, Cos .F
Range:
0.25 - 0.9
Accuracy: ?0.04
Range:
0.90 - 1.0
Accuracy:
?0.03

H2 Frequency Fundamental
Ranges:
40.0 to 70.0 Hz
Accuracy:
?(0.5% + 2 counts)

Harmonics Display
Voltage, Current, Frequency
Ranges:
Fundamental to 51st harmonic
Accuracy:
Fundamental:
VA ?(3% + 2 counts) W ?(5% + 2 counts)
2 to 31st harmonic:
VA ?(5% +3 counts) W ?(10% +10 counts)
32 to 51st harmonic:
VA ?(15% +5 counts) W ?(30% +5 counts)

Frequency Fundamental
Ranges:
40 Hz to 70 Hz
Accuracy:
?0.25 Hz

Phase
Range:
V, A (between Fundamental & Harmonics)
Accuracy:
?3? to ?15?
Range:
W (between Voltage Fundamental & Current Harmonics)
Accuracy
?5? to ?15?

K-factor (Current and Power)
Range:
1.0 to 30.0
Accuracy:
?10%

THD Total Harmonic Distortion
Range:
0.00 - 99.99
Accuracy:
?(3% + 8 counts)

Sags and Swells
Recording times:
4 min to 16 days (selectable)
Vrms Actual, Vrms max, min(AC + DC)
Ranges: 5.000V, 50.00V, 500.0V, 1250V*
Accuracy:
Readings ?(2% +10 counts)

Category Generators & Analyzers
Manufacturer Fluke
Model 43B
Description Power Quality Analyzer
Frequency Y
Watts
Option
Manual
Connector Type
Price £1500